ClearFire-H The New standard in Commercial High-efficiency Firetube Boilers |
|
Controls
The CLEARFIRE-Hs high efficiey is achieved
by employing an advanced Fecralloy burner
designed to premix air and fuel for optimal
combustion. This boiler utilizes Cleaver-Brooks
patented Alufer finned fetubes resulting in
unmatched heat transfer and superior fuel
to-steam efficiecy. Efficieey is 85% on low
pressure steam. With optional economizer
efficiecy is 85% on high pressure steam.
|
CLEARFIRE-H Features
Fully-Modulating with High-Turndown via
Variable Speed Blower
Easily-Tuned, Zero-Governor, Premix Burner
No Dampers or Linkages
Low Emissions (< 30 ppm NOx and < 10 ppm
CO) Advanced Combustion Design Eliminates
Need For Flue Gas Recirculation
High efficiey - Greenhouse Gas Reduction
Direct Spark Ignition
Low Gas Pressure < 14 W.C.
Low Noise < 70 DBA
Single Phase Power 115V or 230V
Natural Gas (UL) or Propane
Controls are CSD-1 Compliant
15# or 150# Steam
CLEARFIRE-H Options
Sealed Combustion
Surface Blow-Off Controls
Chemical Feed Tank
High Pressure Regulator
Integral Feed Water System
Blowdown & Feedwater Valve Assemblies
Economizer Package (High Pressure Steam)
MODBUS (485) Communications
|
advanced Fecralloy Burner
super efficient Patented alufer Finned Firetubes
|
Clearfire-H Boiler Dimensions and Ratings |
Boiler H.P. |
10 |
15 |
20 |
25 |
30 |
40 |
50 |
60 |
Dimentions - INCHES |
Overall Length (A) |
86 |
86 |
87 |
87 |
91.5 |
104 |
110 |
110 |
Overall Width (B) |
43.5 |
43.5 |
47 |
47 |
56 |
56 |
60 |
60 |
Overall Hight (C) |
54 |
54 |
57 |
57 |
65.5 |
65.5 |
69 |
69 |
Stack Norminal (D) |
6 |
6 |
6 |
6 |
6 |
6 |
6 |
6 |
Steam Boiler Weights in LBS |
Normal Water Weight |
1,004 |
1,004 |
1,245 |
1,245 |
1,851 |
2,150 |
2,698 |
2,698 |
Approx. Shipping Weight
(15# Steam) |
2,300 |
2,300 |
2,600 |
2,600 |
3,250 |
3,550 |
5,200 |
5,200 |
Approx. Shipping Weight
(150# Steam) |
2,450 |
2,020 |
2,750 |
2,750 |
3,400 |
3,700 |
5,400 |
5.400 |
Power Requirements (Single Phase, 115 or 230 VAC) |
Blower Motor Size (Watts) |
240 |
335 |
335 |
335 |
335 |
750 |
1200 |
1200 |
Ratings |
Rated Capacity - Steam
(lbs-steam/hr from & at 212 F) |
345 |
518 |
690 |
837 |
1,035 |
1,380 |
1,725 |
2,070 |
Output (1000 Btu/hr) |
335 |
502 |
669 |
837 |
1,004 |
1,339 |
1,674 |
2,008 |
Fuel Input (CFH) - 15#Steam |
394 |
591 |
788 |
985 |
1,181 |
1,575 |
1,696 |
2,363 |
Fuel Input (CFH) - 150#Steam |
404 |
611 |
813 |
1,021 |
1,214 |
1,621 |
2,017 |
2,432 |
|
* Input calculated at norminal 83% efficiency for 1000 BTU gas content
|
|